小电流接地系统故障选线方法
来源:用户上传
作者:
摘 要
小电流接地系统中暂态信号丰富。提取有效的暂态信号进行选线 将提升选线的准确率。本文通过希尔伯特黄变黄对暂态信号进行处理。通过提取各线路零序电流并进行分解处理。对最高频的固有模态函数进行时频分析,比较各线路故障时刻的极性,从而达到选线效果。
关键词
暂态信号;希尔伯特黄变换;零序电流
中图分类号: TM862 文献标识码: A
DOI:10.19694/j.cnki.issn2095-2457 . 2020 . 08 . 48
Abstract
Transient signals are abundant in low-current grounding systems. Extracting valid transient signals for line selection will improve the accuracy of line selection. In this paper, the transient signal is processed by Hilbert yellowing. The zero-sequence current of each line is extracted and decomposed. Time-frequency analysis is performed on the highest frequency natural mode function, and the polarity of each line fault moment is compared to achieve the effect of line selection
Key words
Transient signal; Hilbert yellow transform; zero sequence current
0 引言
小电流接地系统中故障电流较小,故障信息难以提取,是配电网故障选线的一个难题。零序电流中含有大量的暂态分量,HHT通过经验模态分解EMD可以把信号分解为几个固有模态函数IMF分量的和,并对IMF进行Hilbert变换得到有物理意义的瞬时频率。HHT是一种基于信号局部特征的方法,其优点是可以自适应地筛选出IMF分量,从而可以克服小波变换中选取小波基的困难。
1 单相接地故障的暂态零序电流特征分析
系统发生单相接地故障時其结构如图1所示。
发生单相接地故障时,流过故障点的接地电流由暂态电容电流和暂态电感电流两部分组成。因两者在频率上存在明显不同,因此两者在暂态过程中不能够相互补偿,单相接地故障时零序电流暂态过程等值电路图如下。
4 结语
本文采用HHT变换对小电流接地系统进行故障选线,对故障后各线路零序电流经EMD分解,得到若干从高频到低频分量,对各条线路最高频IMF分量进行时频分析,比较各线路故障时刻的极性从而可以正确选线。通过仿真算例验证了该分解方法的完备性,选线原理简单,可以达到选线效果。
参考文献
[1]戴栩生,黄纯,叶倩,等.基于暂态相关性分析的小电流接地故障选线方法[J].中国电力,2015,48(1):81-86.
[2]王磊,骆玮,曹现峰.基于改进EMD算法的小电流接地故障选线[J].电气工程学报,2015,10(8): 29-34,44.
转载注明来源:https://www.xzbu.com/8/view-15205525.htm